Reference product range for solar cables, organized for technical comparison and project enquiries.
Open Air, Buried, In conduit
Key product information for comparison, engineering review and quotation preparation.
Reference specification for H1Z2Z2-K in the Solar Cables range. Confirm final construction, standards and sizing for the actual project before ordering.
| Material | Tinned copper, class 5 (flexible) |
|---|---|
| Conductor | Electrolytic annealed tinned copper, class 5 (flexible) according to IEC 60228 and EN 60228 |
| Insulation | Halogen free cross-linked rubber according to table B1 in Annex B of EN 50618 and IEC 62930 |
| Outer Sheath | Halogen free cross-linked flexible rubber according to table B1 in Annex B of EN 50618 and IEC 62930 |
| Rated Voltage | 1.5 (1.8) kV DC / 1.0/1.0 kV AC |
| Maximum Conductor Temperature | 90 (120 during 20,000 h) °C |
| Maximum Short-Circuit Temperature | 250 (max. 5 s) °C |
| Minimum Service Temperature | -40 (fixed and protected installations) °C |
| Flame Non-Propagation | Flame non-propagation according to EN 60332-1-2 / IEC 60332-1-2 |
| Fire Non-Propagation | Fire non-propagation according to EN 50399 |
| CPR Classification | Cca-s1b, d2, a1 according to EN 50575 |
| Halogen Free | Low Smoke Halogen Free according to EN 60754-1 / IEC 60754-1 |
| Low Corrosive Gases Emission | Low corrosive gases emission according to EN 60754-2 / IEC 60754-2 |
| Low Smoke Emission | Low smoke emission according to EN 61034 / IEC 61034 |
| Light Transmittance | > 60% |
| Minimum Bending Radius | 4x cable diameter (cable diameter ≤ 8 mm), 5x cable diameter (8 12 mm) |
| Impact Resistance | AG2 Medium severity |
| Chemical & Oil Resistance | Excellent |
| UV Resistance | UV Resistant according to EN 50618 and IEC 62930 |
| Water Resistance | AD7+ Immersion, AD8 Submersion |
| Installation Conditions | Open Air, Buried, In conduit |
| Standards (According To) | EN 50618, IEC 62930, UTE C 32-502 |
| Standards and Approvals | TÜV Rheinland, RETIE, AENOR, RoHS, CE |
| Typical Applications | Solar PV installations, Solar farms, Rooftop solar, Floating solar plants |
Reference source: Top Cable public product page. This local entry is a technical reference and does not imply manufacturing ownership of the referenced trademark.
Use-case guidance to understand where this product fits best.
Reference application: Open Air.
Reference application: Buried.
Reference application: In conduit.
Service and manufacturing advantages that support the product decision.
Stable manufacturing and dependable delivery quality.
Practical cable solutions for project-specific use cases.
Balanced cost and product performance for long-term projects.
Fast response before delivery and after project deployment.
Use these quick answers to help technical and commercial teams align faster.
Confirm voltage, conductor construction, installation conditions, required standards and cable sizing for the specific project.
Where the source provides a public datasheet, use the download button and verify that it is the current revision.
Send the reference model and project requirements to the sales team for an equivalent-product review and quotation.
Reference specification for PV LSZH AL 1500V in the Solar Cables range. Confirm final construction, standards and sizing for the actual project before ordering.
Reference specification for H1Z2Z2-K in the Solar Cables range. Confirm final construction, standards and sizing for the actual project before ordering.
Reference specification for PV AL 1500V in the Solar Cables range. Confirm final construction, standards and sizing for the actual project before ordering.